|
|
TROUBLE
WITH YOUR
SUBMERSIBLE
PUMP FOR
DUMMIES
| ||||||||
| BASIC
COMPLAINT 1. No water A. Motor runs - you can hear it or feel the pipe vibrate or amp check if you have an amprobe. a) Hole in drop pipe or coupling, bleeder valve blown out. b) Massive leak in your system. Pump is delivering water just not where you want it to go. c) Jammed or backward check valve. It happens. d) Pump is out of the water e) Pump inlet screen plugged. Very rare. f) Pump worn out. Impellers worn. If it has pumped sand or is very old this is possible. g) Pump shaft broken or coupling stripped. Very rare these days. h) Pump air locked. j) Water level has dropped so far pump can't lift to surface. B. Motor doesn't run a) No power to pump - this is the most common thing. b) Motor failed c) Wires down well broken or bad splice. d) Control box problem, bad capacitor or relay or cover is not on. e) Pressure switch problem - easy to fix but usually wishful thinking. 1) Look at the contacts. If they aren't closed figure out why. The switch thinks the pressure is at shutoff level. Did it freeze last night? Possibly bad pressure switch or plugged inlet. 2) Burned contacts don't mean much. Bugs in the contacts are a common problem. Clean them off with the eraser end of a wooden pencil. These contacts are always electrically hot. f) Overload tripped. Look for a red button on or under control box. g) Pump locked up. h) Both wires to motor or control box are connected to the same leg in the panel. 2. Not enough water, or pressure - motor runs, perhaps runs all the time A. Leaks - surprisingly small leaks can lose a lot of water. Common problem. a) Leaks in your house system. Shut off line between tank and house and see if pump builds up pressure normally. b) Down the well: Holes in drop pipe or bleeder valve. B. Pump problems a) Pump too small for demand b) Pump impellers worn by sand c) Water level has dropped below what pump is designed for d) Check valve jammed either down well or on surface. The nut can also come off the plunger and improper pipe fittings can prevent plunger travel. e) Plugged inlet screen. Very rare. f) No water in well or pump not set deep enough. g) Motor coupling stripped or shaft broken. Sometimes can still pump. C. Tank problems a) Waterlogged tank will cause pump to go on and off continually. This also results in apparent low pressure. This is very common. b) Surface check valve stuck open allowing water to run back down the well or stuck closed preventing water from getting up. D. Electrical problems a) Improper connections at control box. If color codes were not kept the pump will attempt to start on the run winding and will not be able to continue running b) Low voltage. 230 volt pumps will run on 115 volts but not very well and will cut out and reset. This happens when one pole of a two pole circuit breaker has tripped. Pull both poles all the way to off, then back to on. c) Motor has internal short which is not bad enough to make it stop totally but results in intermittent operation or less than full speed operation. This is a frequent motor death mode. 3. Bad water A. Milky -air or gas in water. 1) Natural entrained air or gas - not much you can do about it. 2) Tank air problem a) Bad air volume control b) Pumping water level too low allowing air to be sucked into pump c) Excessive draw from tank allows air into house lines B. Sandy - well problem, made worse by frequent starts, well driller problem C. Tastes bad - try an activated carbon filter D. Looks bad - particulates in water, try a cartridge filter E. Stains sink -Iron and/or manganese in water, water treatment problem F. Stinks - hydrogen sulfide gas or methane G. Slime in strainers - iron bacteria, chlorinate well 4. Fuses blow, breakers trip, overloads trip A. Happens immediately when power applied to motor 1) Short to ground in motor, cables or supply wires to pressure switch. Remove control box cover or disconnect leads to motor to see where the problem is. Shorts make things trip very fast. 2) Worn out breaker, wrong size breaker, non-time delay fuses can't take starting current. 3) Control box problem causing start winding in motor not to operate. Usually times several seconds to trip. 4) Low voltage 5) Pump locked up B. Happens when motor has been running 1) Low voltage 2) Short cycling, too many starts 3) Control box too hot due to sun or other heat source. 4) Control box problem - bad capacitor, relay, or wrong size 5) Fuses or overloads too small. 6) Circuit breakers worn out - they will only trip so many times. 7) Frequent low head starting causing up thrust 8) Worn pump - usually causes low amps but can also cause high amps. 9) Pumping a lot of sand. 10) Wires too small or contacts somewhere very bad causing high voltage drop. 11) Well is so crooked the pump and moor have been forced into a bind. You have to work at it to create this one. 5. Pumps starts and stops too often. This is very hard on submersible pumps and motors. A. Water logged tank. 1) Galvanized tank a) No air charging system - drain tank and open a fitting to break vacuum. This can always be used as a temporary fix on any tank. b) Air leak in tank above water level c) Surface check valve is leaking and preventing snifter valve from taking in air. d) Snifter valve (usually screwed into check valve) is not working. It should suck in air every time the pump stops. Frequent problem area. e) Bleeder in well is not letting water leak out of the pipe so air can be sucked in by the snifter. f) Pump runs constantly and so never cycles to put air in tank. g) Air volume control letting too much air out. 2) Bladder tank a) Bladder is ruptured. Tank will feel heavy and water will come out of tire core valve on top of tank. b) Tank has too little pre-charge air in it or, too much. It needs to be just right which is 2 pounds less than the start pressure of the pump, measured with the tank drained and the pump off. B. Air logged tank - air volume control bad or too much air being pumped in. C. Defective pressure switch or set wrong D. Tank too small for pump size and demand. E. Check valve on surface may be jammed or partially open |
|
| ADVANCED
TROUBLESHOOTING This is for people who are familiar with electricity and have a voltmeter, ammeter and ohmmeter and enough common sense not to fry themselves. There are two basic symptoms: 1) Motor does not run 2) Something trips out 1) Motor does not run A) Makes no sounds - this most likely means no power to motor. First make sure you have put he cover back on the control box if it is 1 HP or less. Start at the pressure switch with the switch wedged open with a non-conductor and measure voltage leg to leg-AND to ground. If you do not have 230 volts (unless it is a rare 115 volt motor) trace back to the circuit breaker or fuse box. If you have 115 volts to ground on both legs at the pressure switch, you have both legs on the same hot leg and thus zero potential difference between them. Put one leg on the other hot leg. If you have 115 volts to ground on one leg and zero on the other, one wire is broken or one half of the 230 volt breaker is defective or tripped. If everything is zero at the pressure switch the wires are broken or the breaker is bad, or tripped, or the main power is out. If everything checks out then there is an open in the motor or in the control box or the wiring to the motor. Start by disconnecting the power at the breaker then di sconnecting the wires that go down the well from the control box. Use an ohm meter to check for continuity between all three wires (or two if it is a two wire pump). Also check each leg to ground. All should be infinity or at least 10 megohms to ground. The resistances leg to leg are small. The yellow is common and the yellow red (start) should be more than the black (run) to yellow. An open indicates a broken wire, bad splice or bad motor. A low resistance to ground indicates a bad motor or sub cables that are damaged. B) Motor hums, buzzes . This is either low voltage, a bad control box, mixed wire color code , shorted motor. Do
all
the
checks
listed
in
(
A)
above.
If
it
is
not
covered
in
(A): 1)
If
the
pump
is
new a) Ohm check the wires from the motor. The highest amp reading will be Red to Black. The next highest Yellow to Red and the lowest Yellow to Black. If your readings don’t agree, the color code is mixed down below. 2)
Wrong
voltage
control
box.
Only
possible
on
½
HP
pumps
where
230
volt
or
115
volt
motors
are
made.
If
115
volt
box
is
used
on a
230
system,
the
control
box
relay
will
be
expecting
much
higher
amps
and
so
will
not
drop
out
the
start
winding. 3)
Control
box
problems.
Sometimes
they
are
bad
out
of
the
box.
11/2
HP
and
above
sometimes
have
incorrect
connections.
Rare
but
it
happens. There
are
four
possible
components
in a
control
box: Start
capacitors-
black
cylinders-
most
likely
to
fail.
Look
for
burned
off
connectors,
black
gunk
oozing
out.
If
it
looks
OK,
you
need
an
analog
ohm
meter.
Short
across
the
capacitor
to
discharge
it,
then
put
the
ohm
meter
on
it.
It
should
show
a
low
reading
which
increases
to
infinity
over
several
seconds
as
the
capacitor
charges.
These
are
cheap
and
readily
available
at
any
electric
motor
shop. Run
capacitors
-
usually
metal
cylinders
-
almost
never
fail-
almost.
Overload
relays
-
“Klixons”
the
red
button.
They
fail.
If
they
trip
out,
check
the
amp
draw.
If
it
is
normal,
the
overload
is
bad.
By-pass
it
with
a
jumper
until
you
can
get
one.
( or
forget
about
it) Start
relay-
black
or
blue
square
.
Most
difficult
to
diagnose.
It
depends
on
whether
they
are
solid
state
(blue,
or
on
some
original,
a
small
semi-
conductor
looking
thing)
or
electro-mechanical,
a
2"
square
with
MARS
written
on
it
somewhere.
See Franklin-electric.com
(www.fele.com)
for
details
on
this.
If
you
get
to
this
point,
just
replace
the
control
box. Control
box
problems
are
often
caused
by
short-cycling
of
the
pump. 2.
Something
trips
out.
This
means
the
pump
overload
or a
circuit
breaker
or
fuse.
This
does
not
mean
the
pressure
switch.
First
check
for
proper
voltage
starting
at
the
circuit
breaker,
then
the
pressure
switch,
then
the
leads
going
down
the
well.
This
can
be
difficult
with
control
boxes
that
have
covers
that
pull
the
guts
out
with
them.
These
are
for
your
safety
and
the
manufacturers
safety
from
lawyers,
but
they
are
a
pain
to
troubleshoot.
People
in
the
industry
make
jumpers
from
two
old
control
boxes.
Your
best
bet
is
to
put
a
short
jumper
on
the
three
pump
leads
and
wire
nut
them
where
you
can
get
a
probe
on
them.
This
also
lets
you
make
amp
readings
and
ohm
readings. A.
Circuit
breaker
trip.
If
there
are
no
voltage
abnormalities,
this
is
either
a
dead
short
somewhere
or a
bad
breaker.
If
it
takes
some
time
to
trip,
look
for
bad
breaker,
too
small
a
breaker
or
hot
breaker
box.
It
may
also
be a
small
ground
fault
resulting
in
high
amps
but
usually
the
pump
overload
will
trip
first.
If
you
are
looking
for
a
short
or
ground
fault,
open
the
circuit
breaker
so
you
don’t
blow
up
your
ohm
meter,
then
start
at
the
pump,
disconnect
the
leads
going
down
the
well
and
check
each
leg
to
ground.
You
should
get
near
infinity.
Next
check
the
yellow
to
red
and
yellow
to
black.
These
reading
should
be
very
low,
2 to
12
Ohms.
The
yellow
to
red
should
be
higher
than
the
yellow
to
black.
The
exact
readings
are
available
from
the Franklin-electric.com
web
site,
but
they
aren’t
that
critical.
If
you
don’t
find
anything
down
the
well,
start
working
your
way
back
to
the
pressure
switch,
then
to
the
breaker,
until
something
shows
up.
Fix
it.
This
will
probably
require
pulling
the
pump
or
digging.
The
good
news
is
that
you
will
get
your
exercise
without
paying
health
club
dues. B.
Overload
trip.
This
means
high
amps
or
bad
overload.
Again,
assuming
nothing
showed
up
on
the
voltage
check,
take
amp
readings
on
all
three
wires.
Look
up
the
service
factor
amps
on Franklin-electric.com,
and
compare.
These
motors
are
actually
designed
for
the
service
factor,
i.e.
a 2
HP
motor
is
actually
a
2.3
HP
motor,
so
it
doesn’t
hurt
them
to
run
at
SFA.
If
the
amps
are
uniformly
high
by
10
to
15%
it
probably
means
the
motor
and/or
pump
end
are
shot.
If
one
leg
is
high
it
indicates
a
ground
fault.
The
red
leg
is
the
start
winding,
the
black
is
the
run
winding
and
the
yellow
is
common.
Any
electrons
that
go
down
the
red
and
black
have
to
come
up
the
yellow
or
go
to
ground.
A
single
high
leg
is
probably
a
ground
fault.
If
you
put
your
amprobe
around
all
three
legs
at
once
and
have
any
current
show,
it
is a
ground
fault.
It
can
be
motor
or
sub
cable.
When
the
motor
starts
you
should
see
a
momentary
blip
on
the
red
lead
amps
which
may
fall
off
to
zero
on
small
pumps,
or
fall
to a
low
level
on
capacitor
start/capacitor
run
control
boxes.
If
you
don’t
see
this,
look
for
control
box
problems
or
an
open
in
the
start
circuit.
This
usually
is
accompanied
by
high
amps
on
the
black-yellow
leads
as
the
pump
tries
to
start.
It
is
possible
for
the
pump
to
start
sometimes
without
the
start
circuit.
|